홈으로이메일koreaengchina
 
EP502
 HOME > PRODUCT > EP502
Characteristics  
  CARE 50 is a blend of propane (R290) and ethane (R170) developed to
replace R22 and R407C
   
Primarily for use in commercial air-conditioning and large refrigeration
  systems that have traditionally used R22.
Operates at similar pressures to R22 and R407C.
Possesses similar volumetric refrigerating effect to R22 and R407C.
Can be used in a R22 or R407C compressors or a specific CARE 50
  compressor.
Can be used with R22 or R407C heat exchangers and expansion 
  devices.
Compatible with most common refrigeration materials and lubricants.
Replacement : R-22, R-404a, HFC-407C, HFC-507
Application Range : All kinds of heat pumps, low/ medium temperature
   commercial refrigeration. Large size chillers in hotels, factories,    department stores, large buildings.
Packing : 500gr/CAN, 3Kg/10 Kg/20 Kg/50 Kg Cylinder, Bulk Tank, ISO   Tank Container
   
Physical Properties  
 
Product EP502 R502 R407C
Chemical Type HC CFC/HFC HFC
Molecular Mass ( Kg/Kmol ) 46.8 111.6 95.0
Density ( Kg/m3 ) ★ 493.5 11192.0 1140
Temperature Range high, medium, low - -
Ozone depletion potential (CFC-11=1) 0 0.28 0
Global warming potential (CO2=1, 100yr ITH) ◇ 3 6200 1610
Normal boiling point (1.0 bar, abs) ★ -49.1℃ -45.4℃ -43.8℃
Latent heat (1.0 bar, abs) ★ 443 kJ/Kg 174 kJ/Kg 186 kJ/Kg
Toxicity None None None
Refrigerant mass charge size (R12=100%) 41% 100% 97%
Lubricant Mineral Mineral Ester
     
  * All conditions given at +25℃ (dew point).
★ Boiling points at standard atmospheric pressure (101.325kPa)
◇ CO2 GWP based on 100 year integration time horizon, defined in the Intergovernmental Panel for Climate Change      (IPCC)
* Scientific Assessment 1994, CO2 = 1.
     
chemsupply@purechem.co.kr